Building Airflow Standard Chart
Volume of habitable space
cubic feet
Occupants (bedrooms +1)
occupants
Climate Zone
zone
Height Correction Factor
factor
# of stories
Height Correction Factor
1
1
1.5
0.89
2
0.81
2.5
0.76
3
0.72
"N" Factor
climate zone multiplied by height correction factor
"N" factor
Building Airflow Standard - Use Greater of Two Methods
1. ((15cfm * # occupants) * āNā) = CFM50
CFM50
CFM50
60
BAS
House CFM50
If final house CFM50 is greater than BAS, no work needs done
Final house CFM 50 between 70% and 100% of BAS, mechanical ventilation recommended
Final house CFM50 less than 70% of BAS, mechanical ventilation required, see below
Minimum Mechanical Ventialtion Rate - Greater of Two Methods
(15cfm * # of occupants)
cfm
(.35 ACH * Volume)
cfm
60
Minimum mechanical ventilation requried (larger of above)
cfm
Wisdom & Associates, Inc.
www.WisdomAndAssociates.com